16 zones fire alarm panel

KSh 34,000.00

16 zones fire alarm panel AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of a conventional fire alarm system, designed for applications requiring smoke detectors, bells, manual pull stations, and sprinkler supervision.

Description

16 zones fire alarm panel Description
16 zones fire alarm panel Control Systems
Introductions:
1. AW-CFP2166-2 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.
2. Adopted modularized design and flexible extendable capacity.
3. Two-level control mode with a lock
4.27VDC power supply output.
5. FIRE PROTECTION, FIRE ROUTING, and FAULT signal output, the output can be configured to dry relay type or wet sources type.
6.2 channel general sounders output.
7. Each zone has 1 circuit detector input.
8. Each zone can be disabled by a button.
9. It has a RESET button to reset the panel.
10. SILENCE button to stop BUZZER and SOUNDERS.
11. EVACUATE button to start a manual fire alarm immediately.
12. TEST button to test all LEDs orderly.
13. Low-battery protection function, when battery voltage is lower than 21VDC, the battery will be cut off automatically until the mains power is on.
14. Optional GSM module is available for fire alarms by SMS.

Asenware, is a professional fire alarm solution provider.

ITEM 1Zone panel 2Zone panel 4-8 Zone panel 12-32 Zone panel
Model No. AW-CFP2166-01 AW-CFP2166-02 AW-CFP2166-04-8 AW-CFP2166-12-32
Power specification
Mains supply voltage 110VAC or 240VAC
Internal power supply 27.2VDC
Total output current limited 500mA @ 240VAC 500mA @ 240VAC 3A @ 240VAC 3A @ 240VAC
Main supply monitor for fault Yes
Battery protection for low voltage Yes
Batteries (default configuration) 12V2AH*2
Detector circuit specification
Number of circuits 1 2 4-16 4-32
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Line fault monitor for detector removal Yes, if End of Line Monitor Unit is fitted in place of End of Line Resistor
End of Line device 6.8k Ω,5% tolerance, 0.25W (color code-blue, grey, red,gold)
Detector continuity diodes Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value 470 to 680 Ω, 0.225 or 0.5 watt
The maximum number of smoke/heat detectors per zone 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if the End of Line Monitor Unit is fitted, for correct operation maximum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zone No limit
Sounder circuit specification
Number of general circuits 2
End of line resistor value 6.8k Ω,5% tolerance, 0.25W (color code-blue, grey, red, gold)
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Outputs fused AT 400mA
Maximum number of bells @ 20mA of each sounder output 20
Fuses
Battery fuse 1.5A F 20mm
Sounder outputs 500mA F 20mm
Fire and fault output
Output type NC and NO relay
Maximum current 100mA
Connection block
Largest acceptable conductor size 2.5mm2
Smallest acceptable conductor size 0.75mm2
Size and weight
Dimensions(mm) 272*200*70mm 320*231*90mm 395X502X124 362X565X124
Weight (without batteries) 4kg 5kg 7kg 8kg
Weight (with batteries) 5.8kg 6.8kgAsenware 2 Zone Conventional Fire Panel

Reviews

There are no reviews yet.

Be the first to review “16 zones fire alarm panel”

Your email address will not be published. Required fields are marked *